BS EN IEC 60305 pdf free download.Insulators for overhead lines with a nominal voltage above 1 000 V – Ceramic or glass insulator units for AC systems – Characteristics of insulator units of the cap and pin type.
The object of this document is to prescribe specified values for the mechanical characteristics and for the main dimensions of string insulator units of the cap and pin type.
The power frequency, lightning impulse and puncture withstand voltages of string insulator units are not specified in this document. lEO 60383-1 gives the electrical characteristics which define string insulator units; their values are agreed between purchaser and manufacturer.
Ball and socket couplings are covered by IEC 60120, clevis and tongue couplings by
IEC 60471.
NOTE For the definition of site pollution severity see IEC TS 60815-1.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60383-1, Insulators for overhead lines with a nominal voltage above 1000 V — Part 1:
Ceramic or glass insulator units for AC systems — Definitions, test methods and acceptance criteria
3 Terms and definitions
No terms and definitions are listed in this document.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
• lEO Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
4 Mechanical characteristics, dimensions and types
String insulator units of the cap and pin type are standardized by the following specified characteristics:
— Specified electromechanical or mechanical failing load (SFL) according to IEC 60383-1;
— maximum nominal diameter of the insulating part;
— nominal spacing;
— minimum nominal creepage distance;
— standard coupling.
The corresponding values are indicated in Table 1, Table 2, Table 3, Table 4 and Table 5.
NOTE I The following points merit attention for insulators for use in polluted areas:
a) even if the creepage distance is the same, the withstand voltage characteristics may change with shed shape of the insulators;
b) even if the string length is the same, the withstand voltage characteristics may decrease with increasing insulator strength due to the lower efficiency of creepage distance for a larger average diameter.
NOTE 2 IEC 60815 gives details on the important parameters of shed profiles for antipollution insulators.
5 Designation and marking with respect to shed profile
Insulators are designated in Table 1, Table 2, Table 3, Table 4 and Table 5 by the letter U followed by a number indicating the specified electromechanical or mechanical failing load in kilonewtons.
The letter B or C which follows specifies a ball and socket or clevis and tongue, respectively. The following letter S or L, if present, specifies a short or long spacing.
The letter P, D, V, or T present for “anti-fog” profile, “aerodynamic” profile, “two-alternating” profile, or “three-alternating” profile, as shown in Figure 1, Figure 2, Figure 3,Figure 4 and Figure 5, respectively.
IEC 60383-1 specifies that insulators shall be marked with the specified electromechanical or mechanical failing load. This load may be indicated by using the first part of the designation given in the first column of Table 1, Table 2, Table 3, Table 4 and Table 5: For instance, the insulator may be marked U 160 for the units U 160 BS, U 160 BL and U 160 BLP.BS EN IEC 60305 pdf free download.